Case study released by CSB – fatal 2008 accident at Goodyear Tire and Rubber plant in Houston, Texas

Published:  28 January, 2011

The report by the US Chemical Safety Board cites a need for emergency drills and the following of pressure vessel codes.

The case study released on the 2008 heat exchanger rupture and ammonia release identifies gaps in facility emergency response training and calls for increased adherence to existing industry codes.  

The accident occurred on June 11, 2008, when an overpressure in a heat exchanger led to a violent rupture of the exchanger, hurtling debris that struck and killed a Goodyear employee walking through the area. The heat exchanger contained pressurized anhydrous ammonia, a colorless, toxic chemical, used as a coolant in the production of synthetic rubber; five workers were exposed to ammonia released by the rupture.

On the day prior to the accident, maintenance work required closing several valves on the heat exchanger. CSB investigators found that workers closed a valve that isolated the exchanger from a relief valve, to replace a burst rupture disk located below the relief valve.

The next day, at about 7:30 a.m. an operator closed another valve — this one blocking a second, automatic pressure control valve – to begin cleaning the process line with steam. Unaware that the isolation valve was also closed – thus leaving no means of relieving excess pressure in the exchanger, pressure continued to increase until the heat exchanger exploded violently.  

Managers ordered the plant evacuated. However, CSB investigators found that on the day of the accident the employee tracking system was not operating properly, making it difficult to quickly account for all employees.

The CSB found that a malfunction in the computerized electronic employee badge tracking system delayed supervisors in immediately retrieving the list of personnel in their area, requiring handwritten lists to be generated. At about 1:20 p.m. an operations supervisor assessing the damage to the incident area discovered a fatally injured employee buried in rubble in a dimly lit area. The CSB case study notes that because the fatally injured employee had been a member of the emergency response team, her absence from the evacuation muster point was not considered unusual.      

CSB Chairperson Rafael Moure-Eraso said, “The absence of this worker had not been noted due to the lack of training and drills on worker headcounts. Plant personnel were not provided with the proper training to effectively manage this emergency. Company procedures called for routine evacuation and shelter-in-place drills four times a year, but such drills were not held for several years prior to the incident. Management’s adherence to company procedures should have allowed for effective communication between all members of the workforce and a more robust emergency response structure.”

The report further notes that maintenance work activity was not properly communicated between maintenance and operations personnel, resulting in a subsequent shift not being notified of the isolation of the pressure relief line.

The CSB’s final report outlines several lessons learned including the need to adhere to existing American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code.

CSB Investigations Supervisor Robert Hall said, “We found the accident likely would not have happened had operators followed the ASME code.  It’s crucial that workers continuously monitor an isolated pressure relief system throughout the course of a repair and reopen blocked valves immediately after the work is completed.”

The CSB’s report notes that the ASME code states; “Overpressure protections shall be continually provided…whenever there is a possibility that the vessel can be over-pressurized by a pressure source.” 

  • Operation Florian

Sign up: eMagazine & eNewsletter

The latest issues in your inbox.

Company Profiles

HazSim - Bringing situational HazMat training to life

HazSim, LLC provides innovative simulation training to ensure your team works safely and effectively. HazSim Pro simulation equipment is in use by hundreds of fire departments, training schools, industrial fire teams, and private trainers across the US, Canada and further afield as well as the US Army.

Revolutionizing fire fighting foam technology

The one-stop resource for fire fighting foam concentrates and custom-designed foam suppression systems hardware.

Advancing rescue technology

The specialist supplier of quality PPE and Rescue Equipment to Emergency Services.

The ultimate in innovation, quality and service

For 60 years Lehavot has been delivering the world’s most advanced fire detection and suppression automatic systems

Trust the best, let us be your foam solution

AUXQUIMIA is a Spanish company whose main activity is the design, manufacture and commercialization of firefighting foam concentrates.

Williams Fire & Hazard Control offers a full line of specialized fire response equipment for oil and gas platforms

From storage tanks and pipeline emergencies to offshore platforms and vessels at sea, Williams' response personnel and specialized equipment quickly address adverse fire emergencies.

Foam fights fire

Europe’s foremost fire fighting foam manufacturer has been developing and producing foams since the 1920s.

The leader in truck-mounted hydraulic platforms

Our mission is to provide the best and the safest solution to professionals that work at height.

The independent alternative

Dafo Fomtec AB is a privately owned company with head office in Stockholm Sweden and manufacturing in Helsingborg in the south of Sweden.

If you want quality, you want Zico

Since its inception Ziamatic Corp has provided the men and women of the fire service with products designed to make their jobs safer and easier.

Calendar

  • 18 April, 2018, 9:00 - 19 April, 2018eRIC